Use este identificador para citar ou linkar para este item: https://ri.ufs.br/jspui/handle/riufs/26086
Registro completo de metadados
Campo DCValorIdioma
dc.contributor.authorAraújo, Josegil Jorge Pereira de-
dc.contributor.authorSantos, Carlos Antônio Cabral dos-
dc.contributor.authorHolanda, Carlos Almir Monteiro de-
dc.contributor.authorDuarte, João Batista Furlan-
dc.contributor.authorVilla, Alvaro Antonio Ochoa-
dc.contributor.authorDutra, José Carlos Charamba-
dc.date.accessioned2026-09-10T20:11:26Z-
dc.date.available2026-09-10T20:11:26Z-
dc.date.issued2017-12-
dc.identifier.citationARAÚJO, J. J. P. et al. Energetic analysis of a commercial absorption refrigeration unit using an ammonia-water mixture. Acta scientiarum - Technology, Maringá, v. 39, n. 4, p. 439–448, out./dez. 2017. DOI: https://doi.org/10.4025/actascitechnol.v39i4.29904. Disponível em: https://periodicos.uem.br//actascitechnol/index.php/ActaSciTechnol/article/view/29904. Acesso em: 10 set. 2026.pt_BR
dc.identifier.issn1807-8664-
dc.identifier.urihttps://ri.ufs.br/jspui/handle/riufs/26086-
dc.description.abstractO sistema de refrigeração por absorção (SRA) da ROBUR®, modelo ACF60, com capacidade de 17,5 kW, foi testado, modelado e simulado em regime permanente. Para simular a carga térmica um sistema de aquecimento com refrigerante secundário foi utilizado, e através de um controlador programável lógico (CLP) foi mantida a temperatura de entrada da água no evaporador ao redor de 285,15 K. O modelo matemático foi baseado nas equações de balanço de massa, energia e concentração de amônia, e completado pelas equações de fechamento, tais como, a equação de resfriamento de Newton. O modelo matemático foi implementado no Engineering Equation Solver - EES®. Os resultados obtidos com a modelagem e simulação numérica permanente são estudados usando o diagrama de Duhring. Potenciais pontos de recuperação de calor interno são visualizados. Os pontos de estados termodinâmicos monitorados são visualizados com os gráficos de mistura binária. Os dados obtidos nas simulações numéricas do SRA foram comparados com os obtidos nos testes reais do sistema com o chiller ROBUR®.por
dc.languageengpt_BR
dc.publisherPró-Reitoria de Pesquisa de Pós-Graduação da Universidade Estadual de Maringápt_BR
dc.relation.ispartofActa scientiarum - Technologypt_BR
dc.subjectAir conditioningeng
dc.subjectAbsorption systemeng
dc.subjectSimulationeng
dc.subjectExperimental resultseng
dc.subjectCOPeng
dc.subjectAr condicionadopor
dc.subjectSistema de absorçãopor
dc.subjectSimulaçãopor
dc.subjectResultados experimentaispor
dc.titleEnergetic analysis of a commercial absorption refrigeration unit using an ammonia-water mixturept_BR
dc.title.alternativeAnálise energética de um chiller de refrigeração por absorção comercial utilizando a mistura amônia-águapor
dc.typeArtigopt_BR
dc.identifier.licenseCreative Commons Atribuição 4.0 Internacional (CC BY 4.0)pt_BR
dc.description.resumoThe ROBUR® absorption refrigeration system (ARS), model ACF60, with a capacity of 17.5 kW, is tested, modeled and simulated in the steady state. To simulate the thermal load a heating system with secondary coolant was used, in which a programmable logic controller (PLC) kept the inlet temperature EVAat around 285.15 K. The mathematical model used was based on balancing the mass, energy and ammonia concentrations and completed by closing equations such as, Newton's cooling equation. The mathematical model was implemented using the Engineering Equation Solver – EES®. The results obtained after modeling and a numerical permanent simulation are studied using the Duhring diagram. Potential points of internal heat recovery are visualized, and by using graphs of the binary mixture, it is possible to identify the thermodynamic states of all monitored points. The data obtained in the numerical simulation of the ARS wascompared with data acquired in the actual tests of the ARS with the ROBUR® apparatus.pt_BR
dc.description.localMaringápt_BR
dc.identifier.doihttps://doi.org/10.4025/actascitechnol.v39i4.29904-
Aparece nas coleções:DMEC - Artigos de periódicos

Arquivos associados a este item:
Arquivo Descrição TamanhoFormato 
EnergeticAnalysisCommercialAbsorptionRefrigeration.pdf1,05 MBAdobe PDFThumbnail
Visualizar/Abrir


Os itens no repositório estão protegidos por copyright, com todos os direitos reservados, salvo quando é indicado o contrário.